POWER SUPPLY SYSTEMSSPDs Type 2DEHNguard® T / DEHNguard®
T FMUDG T 385
Dimension drawing UDG T ...Basic circuit diagram UDG T ...
High discharge capacity due to powerful zincoxide varistorQuick response
Two-part unit, consisting of a base part and plug-in protection component
Reliable control due to \"Thermo Dynamic Control\"disconnector
Energy-coordinated within the Red/Line productfamily
UDG T ...: Single-pole, pluggable surge arrester, consisting of a base part and plug-in protectionmodule
UDG T 385
SPD according to EN 613-11SPD according to IEC 613-1Max. continuous ac voltage    [UC]Max. continuous dc voltage    [UC]Nominal discharge current (8/20 µs)    [In]Max. discharge current (8/20 µs)    [Imax]Voltage protection level    [UP]Voltage protection level at 5 kA    [UP]Response time    [tA]
Max. mains-side overcurrent protection
Short circuit withstand capability at max. mains-side overcurrentprotection
Operating temperature range    [TU]Cross-sectional area (min.)Cross-sectional area (max.)Mounting onEnclosure materialDegree of protectionDimension
Approvals, CertificationsOrdering informationTypePart No.Packing unit
UDG T 385900 11 pcs.Type 2Class II385 V500 V20 kA40 kA<= 1.75 kV<= 1.35 kV<= 25 ns125 A gL/gG25 kArms-40°C...+80°C
1,5 mm2 solid/flexible35 mm2 stranded/25 mm2 flexible35 mm DIN rail acc. to EN 60715red thermoplastic, UL 94 V-0
IP 201 mod., DIN 43KEMA, VDE, UL